The IFM PM1114 is a flush pressure sensor designed for reliable higher-pressure measurement in hygienic process environments. It provides a factory default range of 0...232 psi and supports an extended measurement range. The sensor combines scalable 4...20 mA output with IO-Link communication. Its flush design supports hygienic process integration and cleaning requirements. PM1114 is suitable for automated pressure monitoring where dependable measurement and digital diagnostics are required.
Explore performance details, construction highlights, applications, and technical information in one clear overview.
PM1114 provides a factory default range of 0...232 psi. Its IO-Link range extends beyond the standard factory range for flexible digital monitoring. The sensor has an overload rating of 1085 psi and a burst pressure of 2175 psi. This provides a robust operating margin for industrial pressure systems. The configuration is suitable for process applications where pressure variations need to be monitored continuously.
The flush sensing arrangement helps support hygienic process installation. Stainless-steel construction provides durability in demanding production environments. The design reduces potential contamination points around the sensing surface. It can be integrated into process equipment requiring regular cleaning. The compact configuration also supports installation in machinery and process lines.
The PM1114 supports scalable 4...20 mA analogue communication and IO-Link. IO-Link provides digital process values, parameterisation and diagnostic functionality. This allows the sensor to be connected to modern PLC and automation architectures. Analogue output also supports conventional control systems. The combination provides flexibility for new installations and system upgrades.
0...232 psi factory range
Flush pressure sensing
4...20 mA scalable output
IO-Link communication
1085 psi overload rating
2175 psi burst pressure
Stainless-steel construction
Hygienic process integration
Digital diagnostics
Parameterisation through IO-Link
Continuous pressure monitoring
Industrial automation compatibility
Process pressure monitoring
Food and beverage plants
Hygienic machinery
Filling systems
Pumping systems
Process pipelines
Liquid pressure measurement
Production equipment
PLC control systems
Machine monitoring
Process automation
Industrial instrumentation
| Specification | PM1114 |
|---|---|
| Product type | Flush pressure sensor |
| Model | PM1114 |
| Product family | PM11 |
| Factory range | 0...232 psi |
| Full range | -14.5...232 psi |
| IO-Link range | -14.5...243.7 psi |
| Resolution | 0.076 psi |
| Overload pressure | 1085 psi |
| Burst pressure | 2175 psi |
| Output | 4...20 mA |
| Communication | IO-Link |
| Output type | Scalable |
| Pressure type | Relative |
| Measuring principle | Electronic |
| Sensing design | Flush |
| Housing | Stainless steel |
| Process use | Hygienic |
| Installation | Process connection |
| Digital configuration | Supported |
| Diagnostics | IO-Link |
| Process data | Digital |
| Signal type | Analogue/digital |
| Mounting | Process mounted |
| Automation | PLC compatible |
| Typical use | Process pressure control |