AX series is a Hanyoung NUX temperature controller for monitoring and regulating process temperature. The available configuration is built around the listed sensor inputs, control method and output arrangement, with model information of AX series. Control output: Relay output | • 1a contact, 3 A 240 V a.c., 3 A 30 V d.c. (resistive load) • You can select max. 3 relay outputs, and relay control output is output as RLY1. 2 alarm output contacts (AL1, AL2), loop break alarm (LBA) output assigned by user among RLY1, RLY2, RLY3.; Current output (SCR): 4 - 20 ㎃ d.c. (resistive load max. 600 Ω); Control output operation: Direct/reverse actions ※ selection by parameter setting; Control output: Relay/voltage pulse (SSR) outputs ※ selection by parameter setting.
For panel and process selection, the important characteristics are the input sensor type, control response, power requirements and display or communication options. Display accuracy: ±0.3 % of F.S ±1 digit (in case of R type, ±1.0 % of ±1 digit in the 0 ~ 600 ℃ range); Weight: 320g | 320g | 180g | 300g | 400g; Size: 2 | 48(W) x 96(H) x 63(D) ㎜; Product dimensions: W | 48.0 | 96.0 | 48.0 | 72.0 | 96.0.
Key strengths of the AX series come from the combination of its functional configuration and practical installation specifications. The following characteristics highlight the values that matter most when comparing the product with equipment requirements.
Input voltage: Max. 10 V d.c.; Control output: Relay output | • 1a contact, 3 A 240 V a.c., 3 A 30 V d.c. (resistive load) • You can select max. 3 relay outputs, and relay control output is output as RLY1. 2 alarm output contacts (AL1, AL2), loop break alarm (LBA) output assigned by user among RLY1, RLY2, RLY3.; Power voltage: A | 100 - 240 V a.c. 50/60 Hz; Sampling cycle: 0.1 sec; Display accuracy: ±0.3 % of F.S ±1 digit (in case of R type, ±1.0 % of ±1 digit in the 0 ~ 600 ℃ range).
The AX series is specified by its sensor input, control output, electrical supply, sampling behaviour and accuracy. These values determine how the controller measures temperature and applies its selected control response. Output selection: 1 | SSR + Relay1 + Relay2 | When using relay or SSR output (selection by internal parameter); Sampling cycle: 0.1 sec; Input voltage: Max. 10 V d.c.; Voltage fluctuation rate: ±10 % of power voltage.
Additional technical characteristics include Power consumption: Max. 5.5 VA; Power voltage: A | 100 - 240 V a.c. 50/60 Hz.
The physical design of AX series should be considered together with the installation environment and the available mounting or display arrangement. Panel cutout: W1 * | 45.0 | 92.0 | 45.0 | 68.0 | 92.0; Insulation resistance: Min. 20 ㏁, 500 V d.c. for 1 min (primary terminal - secondary terminal); Dielectric strength: 2,300 V a.c. 50/60Hz, for 1 min (primary terminal - secondary terminal); Ambient temperature & humidity: -5 ~ 50 ℃, 35 ~ 85 % RH (without condensation).
Further construction and environmental details include Vibration resistance: 10 - 55 Hz, single amplitude 0.75 mm, 2 hours in each of 3 axis directions; Shock resistance: 300 m/s² to 3 directions each 3 times.
Integration of AX series requires the correct sensor input, control output, supply voltage and configuration settings for the application. Input voltage: Max. 10 V d.c.; Control output: Relay output | • 1a contact, 3 A 240 V a.c., 3 A 30 V d.c. (resistive load) • You can select max. 3 relay outputs, and relay control output is output as RLY1. 2 alarm output contacts (AL1, AL2), loop break alarm (LBA) output assigned by user among RLY1, RLY2, RLY3.; Power voltage: A | 100 - 240 V a.c. 50/60 Hz; Sampling cycle: 0.1 sec.
Additional operating and interface details include Display accuracy: ±0.3 % of F.S ±1 digit (in case of R type, ±1.0 % of ±1 digit in the 0 ~ 600 ℃ range); Power consumption: Max. 5.5 VA; Current output (SCR): 4 - 20 ㎃ d.c. (resistive load max. 600 Ω). These values provide a practical reference for wiring, setup and normal operation within the selected configuration.
Choose AX series by confirming the exact model or configuration against the required operating conditions. The available model information is AX series. Model: Code | Content; Input voltage: Max. 10 V d.c.; Control output: Relay output | • 1a contact, 3 A 240 V a.c., 3 A 30 V d.c. (resistive load) • You can select max. 3 relay outputs, and relay control output is output as RLY1. 2 alarm output contacts (AL1, AL2), loop break alarm (LBA) output assigned by user among RLY1, RLY2, RLY3.; Power voltage: A | 100 - 240 V a.c. 50/60 Hz.
Before installation, confirm Sampling cycle: 0.1 sec; Display accuracy: ±0.3 % of F.S ±1 digit (in case of R type, ±1.0 % of ±1 digit in the 0 ~ 600 ℃ range); Power consumption: Max. 5.5 VA. Matching the model, electrical ratings, signal requirements, physical arrangement and environmental limits helps keep the product within its specified operating conditions.
| Specification | Details |
|---|---|
| Classification | AX2 | AX3 | AX4 | AX7 | AX9 |
| Input | Thermocouple | K, J, R, T (selection by internal parameter) |
| RTD | Pt100 Ω (selection by internal parameter) |
| Allowable line resistance | Max. 10 Ω/1 wire (RTD). Resistances among 3 wires should be same |
| Sampling cycle | 0.1 sec |
| Impedance | Max. 1 ㏁ |
| Input voltage | Max. 10 V d.c. |
| Display accuracy | ±0.3 % of F.S ±1 digit (in case of R type, ±1.0 % of ±1 digit in the 0 ~ 600 ℃ range) |
| Control output | Relay output | • 1a contact, 3 A 240 V a.c., 3 A 30 V d.c. (resistive load) • You can select max. 3 relay outputs, and relay control output is output as RLY1. 2 alarm output contacts (AL1, AL2), loop break alarm (LBA) output assigned by user among RLY1, RLY2, RLY3. |
| SSR out put | Time share cycle control (CYC) | 12 - 15 V d.c. pulse voltage (resistive load min. 600 Ω) |
| Current output (SCR) | 4 - 20 ㎃ d.c. (resistive load max. 600 Ω) |
| Control | Control type | PID control (by auto-tuning), P control, ON/OFF control |
| Auto-tuning | PID operation by auto-tuning |
| ON/OFF control | When PV > SV, 0% output. When PV < SV, 100% output (only when control hysteresis is 0) |
| Manual reset | User set within 0.0% to 100.0% range |
| Control output operation | Direct/reverse actions ※ selection by parameter setting |
| Control output | Relay/voltage pulse (SSR) outputs ※ selection by parameter setting |
| Power | Power voltage | 100 - 240 V a.c., 50/60 Hz |
| Voltage fluctuation rate | ±10 % of power voltage |
| Insulation resistance | Min. 20 ㏁, 500 V d.c. for 1 min (primary terminal - secondary terminal) |
| Dielectric strength | 2,300 V a.c. 50/60Hz, for 1 min (primary terminal - secondary terminal) |
| Power consumption | Max. 5.5 VA |
| Ambient temperature & humidity | -5 ~ 50 ℃, 35 ~ 85 % RH (without condensation) |
| Vibration resistance | 10 - 55 Hz, single amplitude 0.75 mm, 2 hours in each of 3 axis directions |
| Shock resistance | 300 m/s² to 3 directions each 3 times |
| Weight | 320g | 320g | 180g | 300g | 400g |
| Model | Code | Content |
| AX | - | Universal Input Digital Temperature Controller |
| Size | 2 | 48(W) x 96(H) x 63(D) ㎜ |
| 3 | 96(W) x 48(H) x 63(D) ㎜ |
| 4 | 48(W) x 48(H) x 63(D) ㎜ |
| 7 | 72(W) x 72(H) x 63(D) ㎜ |
| 9 | 96(W) x 96(H) x 63(D) ㎜ |
| Output selection | 1 | SSR + Relay1 + Relay2 | When using relay or SSR output (selection by internal parameter) |
| 2 | SSR + Relay1 + Relay2 + Relay3 |
| 1B | SSR + Relay1(Form c) + Relay2 | Only for AX2, 3, 7, 9 |
| 2B | SSR + Relay1(Form c) + Relay2 + Relay3 |
| 3 | 4 - 20 ㎃ + Relay2 | When using current output |
| 4 | 4 - 20 ㎃ + Relay2 + Relay3 |
| Power voltage | A | 100 - 240 V a.c. 50/60 Hz |
| Classification | Type | AX2 | AX3 | AX4 | AX7 | AX9 |
| Product dimensions | W | 48.0 | 96.0 | 48.0 | 72.0 | 96.0 |
| H | 96.0 | 48.0 | 48.0 | 72.0 | 96.0 |
| D | 63.0 | 63.0 | 63.0 | 63.0 | 63.0 |
| D1 | 5.5 | 5.5 | 5.5 | 5.5 | 5.5 |
| Panel cutout | W1 * | 45.0 | 92.0 | 45.0 | 68.0 | 92.0 |
| H1 * | 92.0 | 45.0 | 45.0 | 68.0 | 92.0 |
| A | 70.0 | 122.0 | 60.0 | 83.0 | 117.0 |
| B | 122.0 | 70.0 | 60.0 | 100.0 | 117.0 |
| No | Type | Category | Title | File |
| 1 | Manual > Instruction Manual | Temperature Controllers | AX series Instruction manual |
| 1 | CAD > 2D | Temperature Controllers | AX series (2D) |
| 2 | CAD > 3D | Temperature Controllers | AX series (3D) |
| No | Mark | Category | Title | File |
| 1 | Certification > CE | Temperature Controllers | AX series (EMC) |
| 2 | Declaration > ROHS | Temperature Controllers | AX series |