MA4SD

HANYOUNG NUX Electricals Timer / Counter

MA4SD

MA4SD is a Hanyoung NUX counter / timer for counting and timing operations. Key specifications include Operating time range: 1 ~ 300 Sec; Power voltage: 100-240 V a.c. 50/60Hz, 24-240 V d.c..
  • Brand HANYOUNG NUX
  • Category Electricals
  • Subcategory Timer / Counter
Interested in this product? MA4SD
Product insights

Everything you need to evaluate this product

Explore performance details, construction highlights, applications, and technical information in one clear overview.

Quality assured Technical details Industrial use Expert support

Product Overview

MA4SD is a Hanyoung NUX counter / timer for counting events and controlling time-based operations. Its model configuration determines the input method, timing or counting range, display and output functions, with model information of MA4SD | MA4SDI. Operating time range: 1 ~ 300 Sec; Power voltage: 100-240 V a.c. 50/60Hz, 24-240 V d.c.; Allowable voltage fluctuation rate: ±10 % of power voltage; Power consumption: Approx. 3.8 VA (100-240 V a.c. 60 Hz), Approx. 1.9 W (24-240 V d.c.).

The operating range, signal conditions, display format, computation speed and connection method should be checked against the machine sequence before installation. Weight: Approx. 95 g (Including fixing bracket); Insulation resistance: Min. 100 MΩ (500 V d.c. Mega standard, conductive terminal - exposed unfilled metal part); Dielectric strength: 2000 V a.c. 50/60 ㎐ for 2 min (conductive terminal - exposed unfilled metal part); Noise immunity: ±2 kV (among operation power terminals, pulse width ±1 ㎲, square wave noise by noise simulator).

Key Features

Key strengths of the MA4SD come from the combination of its functional configuration and practical installation specifications. The following characteristics highlight the values that matter most when comparing the product with equipment requirements.

Operating time range: 1 ~ 300 Sec; Power voltage: 100-240 V a.c. 50/60Hz, 24-240 V d.c.; Control output: Opera tion mode | Power ON Start; Allowable voltage fluctuation rate: ±10 % of power voltage; Power consumption: Approx. 3.8 VA (100-240 V a.c. 60 Hz), Approx. 1.9 W (24-240 V d.c.).

  • Operating time range: 1 ~ 300 Sec
  • Power voltage: 100-240 V a.c. 50/60Hz, 24-240 V d.c.
  • Control output: Opera tion mode | Power ON Start
  • Allowable voltage fluctuation rate: ±10 % of power voltage
  • Power consumption: Approx. 3.8 VA (100-240 V a.c. 60 Hz), Approx. 1.9 W (24-240 V d.c.)
  • Contact capacity: 250 V a.c. 5 A resisitive load
  • Control output: SD | ㅅ(Star) output, △ (Delta) output

Technical Characteristics

The MA4SD technical characteristics define the supported input conditions, counting or timing range, display resolution, computation speed and output behaviour. These values determine how the unit responds to machine signals. Control output: Opera tion mode | Power ON Start; Contact capacity: 250 V a.c. 5 A resisitive load; Control output: SD | ㅅ(Star) output, △ (Delta) output; Operating time range: 1 ~ 300 Sec.

Additional technical characteristics include Power voltage: 100-240 V a.c. 50/60Hz, 24-240 V d.c.; Allowable voltage fluctuation rate: ±10 % of power voltage; Power consumption: Approx. 3.8 VA (100-240 V a.c. 60 Hz), Approx. 1.9 W (24-240 V d.c.).

Design and Construction

The physical design of MA4SD should be considered together with the installation environment and the available mounting or display arrangement. Vibration resistance: 10 - 55 ㎐ (for 1 min), double amplitude 0.75 ㎜ X·Y·Z each direction 1 hour; Shock resistance: 300 m/s² (30G) X·Y·Z each direction 3 times; Ambient temperature: -10 ~ 55 ℃ (icing or dew condensation not allowed); Storage temperature: -25 ~ 65 ℃ (icing or dew condensation not allowed).

Further construction and environmental details include Ambient humidity: 35 ~ 85 % RH.

Integration and Operation

Integration of MA4SD begins with matching its connection, input or control signal and output requirements to the surrounding equipment. Operating time range: 1 ~ 300 Sec; Power voltage: 100-240 V a.c. 50/60Hz, 24-240 V d.c.; Control output: Opera tion mode | Power ON Start; Allowable voltage fluctuation rate: ±10 % of power voltage.

Additional operating and interface details include Power consumption: Approx. 3.8 VA (100-240 V a.c. 60 Hz), Approx. 1.9 W (24-240 V d.c.); Contact capacity: 250 V a.c. 5 A resisitive load; Control output: SD | ㅅ(Star) output, △ (Delta) output. These values provide a practical reference for wiring, setup and normal operation within the selected configuration.

Selection and Use

Choose MA4SD by confirming the exact model or configuration against the required operating conditions. The available model information is MA4SD | MA4SDI. Model: MA4SD | MA4SDI; Model: Code | Content; Operating time range: 1 ~ 300 Sec; Power voltage: 100-240 V a.c. 50/60Hz, 24-240 V d.c..

Before installation, confirm Control output: Opera tion mode | Power ON Start; Allowable voltage fluctuation rate: ±10 % of power voltage; Power consumption: Approx. 3.8 VA (100-240 V a.c. 60 Hz), Approx. 1.9 W (24-240 V d.c.). Matching the model, electrical ratings, signal requirements, physical arrangement and environmental limits helps keep the product within its specified operating conditions.

SpecificationDetails
ModelMA4SD | MA4SDI
Power voltage100-240 V a.c. 50/60Hz, 24-240 V d.c.
Allowable voltage fluctuation rate±10 % of power voltage
Power consumptionApprox. 3.8 VA (100-240 V a.c. 60 Hz), Approx. 1.9 W (24-240 V d.c.)
Return timeMax. 100 ms
Operating time range1 ~ 300 Sec
Operating time errorRepetition error : max. ±0.3 %, Setting error : max. ±5 %, Voltage error : max. ±0.5 %, Temperature tolerance : max. ±2 % (ratio of maximum scale)
△ Conversion time errorMax. ±25 %
Control outputOpera tion mode | Power ON Start
Contact configu rationㅅ Contacts : 1a, △ Contacts : 1a | ㅅ Contacts : 1a, △ contacts : 1a, instantaneous contacts : 1a
Contact capacity250 V a.c. 5 A resisitive load
Relay life▪Mechanical : min. 5 million times ▪Electrical : min. 100,000 times (250 V a.c. 5 A resisitive load)
Insulation resistanceMin. 100 MΩ (500 V d.c. Mega standard, conductive terminal - exposed unfilled metal part)
Dielectric strength2000 V a.c. 50/60 ㎐ for 2 min (conductive terminal - exposed unfilled metal part)
Noise immunity±2 kV (among operation power terminals, pulse width ±1 ㎲, square wave noise by noise simulator)
Vibration resistance10 - 55 ㎐ (for 1 min), double amplitude 0.75 ㎜ X·Y·Z each direction 1 hour
Shock resistance300 m/s² (30G) X·Y·Z each direction 3 times
Ambient temperature-10 ~ 55 ℃ (icing or dew condensation not allowed)
Storage temperature-25 ~ 65 ℃ (icing or dew condensation not allowed)
Ambient humidity35 ~ 85 % RH
WeightApprox. 95 g (Including fixing bracket)
ModelCode | Content
MA4Analog Multi Timer (Star-Delta Timer), 48 (W) × 48 (H) ㎜
Control outputSD | ㅅ(Star) output, △ (Delta) output
SDIInstantaneous output, Υ(Star) output, △(Delta) output
NoType | Category | Title | File
1Manual > Instruction Manual | Counter / Timer | MA4SD Users manual
NoMark | Category | Title | File
1Certification > CE | Counter / Timer | MA4SD (EMC)
Setting errormax. ±5 %,
Voltage errormax. ±0.5 %,
Temperature tolerancemax. ±2 % (ratio of maximum scale)
ㅅ Contacts1a, △ Contacts : 1a
ㅅ Contacts1a, △ contacts : 1a, instantaneous contacts : 1a