Explore performance details, construction highlights, applications, and technical information in one clear overview.
SM100 Board type multi channel Temperature controller is a Hanyoung NUX temperature controller for monitoring and regulating process temperature. The available configuration is built around the listed sensor inputs, control method and output arrangement, with model information of SM100 -□A20 | SM100 -□A16 | SM100 -□A12. Hysteresis: 0 to 120.0 ℃ (with ON/OFF control) ); Hysteresis: 0 ℃ to 120.0 ℃; Control output channel: 20 channel | 16 channel | 12 channel; Control output: Output type | Voltage pulse output for SSR drive (drive voltage : 12 V d.c., load resistance of 600 Ω or more).
For panel and process selection, the important characteristics are the input sensor type, control response, power requirements and display or communication options. Display accuracy: Maximum range ± 0.5 % (± 0.5 % of F.S); Setting and display: Setup method | Setup using acommunication program; Display LEDs: Power display, communication display, control output display; Data length: 8 Bit.
Key strengths of the SM100 Board type multi channel Temperature controller come from the combination of its functional configuration and practical installation specifications. The following characteristics highlight the values that matter most when comparing the product with equipment requirements.
Measure ment input: Input type | Thermocouple (K), range : -199.9 ℃ ~ 999.9 ℃ RTD (Pt100 Ω), range : -199.9 ℃ ~ 640.0 ℃; Control output channel: 20 channel | 16 channel | 12 channel; Power supply voltage fluctuation rate: ±10% of rated power voltage; Display accuracy: Maximum range ± 0.5 % (± 0.5 % of F.S); Power consumption: 25 VA MAX..
The SM100 Board type multi channel Temperature controller is specified by its sensor input, control output, electrical supply, sampling behaviour and accuracy. These values determine how the controller measures temperature and applies its selected control response. Proportional cycle (output cycle): 1 to 100 seconds; Control output action: Select cooling control (Direct action) / heating control (reverse action); Emergency output: 0.0 to 100.0 %; Event output: Number of output points | 1a 3 points (AL1, AL2, AL3).
Additional technical characteristics include Output action: ON/OFF action; Output type: Relay output; Contact capacity: 5 A 250 V a.c. (5 A 30 V d.c.).
The physical design of SM100 Board type multi channel Temperature controller should be considered together with the installation environment and the available mounting or display arrangement. Case material: Cold rolled steel plate (SPC); Weight: Approximately 1,000g; Insulation resistance: 20 MΩ Min. Power and ground terminals (500 V d.c. in megaohms); Dielectric strength: 2,000 V a.c. for 1 minute; power and ground terminals.
Further construction and environmental details include Ambient temperature: 0 to 50 ℃; Ambient humidity: 50 to 85 % RH (however, there should be no condensation); Storage temperature: -20 to 70 ℃ (however, there should be no condensation).
Integration of SM100 Board type multi channel Temperature controller requires the correct sensor input, control output, supply voltage and configuration settings for the application. Commu nication protocol: PC Link with SUM; Response time: Receiving processing time + (response set time x 25 ㎳); Sampling frequency: 1 second; Power supply voltage fluctuation rate: ±10% of rated power voltage.
Additional operating and interface details include Power consumption: 25 VA MAX.. These values provide a practical reference for wiring, setup and normal operation within the selected configuration.
Choose SM100 Board type multi channel Temperature controller by confirming the exact model or configuration against the required operating conditions. The available model information is SM100 -□A20 | SM100 -□A16 | SM100 -□A12. Model: SM100 -□A20 | SM100 -□A16 | SM100 -□A12; Vibration (durabilit): 10 Hz ~ 55 Hz 19.6 m/s² 3 axis 6 directions 2 h; Shock (durabilit): 196 m/s², 3 times in each of 6 directions of 3 axes; Measure ment input: Input type | Thermocouple (K), range : -199.9 ℃ ~ 999.9 ℃ RTD (Pt100 Ω), range : -199.9 ℃ ~ 640.0 ℃.
Before installation, confirm Control output channel: 20 channel | 16 channel | 12 channel; Power supply voltage fluctuation rate: ±10% of rated power voltage; Display accuracy: Maximum range ± 0.5 % (± 0.5 % of F.S). Matching the model, electrical ratings, signal requirements, physical arrangement and environmental limits helps keep the product within its specified operating conditions.
| Specification | Details |
|---|---|
| Model | SM100 -□A20 | SM100 -□A16 | SM100 -□A12 |
| Control output channel | 20 channel | 16 channel | 12 channel |
| Measure ment input | Input type | Thermocouple (K), range : -199.9 ℃ ~ 999.9 ℃ RTD (Pt100 Ω), range : -199.9 ℃ ~ 640.0 ℃ |
| Display accuracy | Maximum range ± 0.5 % (± 0.5 % of F.S) |
| R.J.C precision | Within display precision |
| Sampling frequency | 1 second |
| Input calibration | -1200.0 ℃ to 1200.0 ℃ |
| Input filter | 0.0 to 120.0 seconds |
| Burn-out action | Thermocouple : Upscale RTD : Upscale |
| Setting and display | Setup method | Setup using acommunication program |
| Number of setting | 20 points | 16 points | 12 points |
| Memory Storage | Storage using semiconductors |
| Device address settings | Setup using the built-in HEX BCD switch (1 to 15) |
| Display LEDs | Power display, communication display, control output display |
| Control output | Output type | Voltage pulse output for SSR drive (drive voltage : 12 V d.c., load resistance of 600 Ω or more) |
| Control action | Time division proportion PID or ON/OFF control |
| Number of PID groups | 1 group / channel |
| Proportional cycle (output cycle) | 1 to 100 seconds |
| Proportional band (P) | 0 to 1200.0 ℃ |
| Integral time (I) | 1 to 3600 seconds |
| Derivative time (D) | 1 to 3600 seconds |
| Anti-Reset Windup(A.R.W) | 0.1 to 100.0 % ※ “0” setting (Auto) |
| Manual reset | 0.0 to 100.0 % (with ON/OFF control) |
| Hysteresis | 0 to 120.0 ℃ (with ON/OFF control) ) |
| Control output action | Select cooling control (Direct action) / heating control (reverse action) |
| Emergency output | 0.0 to 100.0 % |
| Event output | Number of output points | 1a 3 points (AL1, AL2, AL3) |
| Control action types | 1a 3 points (AL1, AL2, AL3) |
| Loop burnout alarm | 0 to 7200 seconds (OFF when set to "0") |
| Hysteresis | 0 ℃ to 120.0 ℃ |
| Output action | ON/OFF action |
| Output type | Relay output |
| Contact capacity | 5 A 250 V a.c. (5 A 30 V d.c.) |
| Digital input | Number of external contact inputs | 1 point (RUN / STOP according to the built-in dip switch) |
| Commu nication specifi cation | RS485/ 422 | Commu nication standards | ELA-RS485/422 (4-Wire type) |
| Commu nication method | Half duplex |
| Maximum number of connections | 15 units ※ Address setting method using the HEX BCD switch |
| Commu nication sequence | No sequence |
| Start bit | 1 Bit |
| Stop bit | 1 Bit |
| Parity bit | Even |
| Data length | 8 Bit |
| Transmission speed | 19200 bps |
| Commu nication distance | 1.2 ㎞ MAX |
| Commu nication protocol | PC Link with SUM |
| Response time | Receiving processing time + (response set time x 25 ㎳) |
| General specifi cation | Power voltage | 100 V - 240 V a.c. 50/60 Hz |
| Power supply voltage fluctuation rate | ±10% of rated power voltage |
| Power consumption | 25 VA MAX. |
| Insulation resistance | 20 MΩ Min. Power and ground terminals (500 V d.c. in megaohms) |
| Dielectric strength | 2,000 V a.c. for 1 minute; power and ground terminals |
| Ambient temperature | 0 to 50 ℃ |
| Ambient humidity | 50 to 85 % RH (however, there should be no condensation) |
| Storage temperature | -20 to 70 ℃ (however, there should be no condensation) |
| Vibration (durabilit) | 10 Hz ~ 55 Hz 19.6 m/s² 3 axis 6 directions 2 h |
| Shock (durabilit) | 196 m/s², 3 times in each of 6 directions of 3 axes |
| Case material | Cold rolled steel plate (SPC) |
| Installation | Fasten using screws |
| Weight | Approximately 1,000g |
| No | Type | Category | Title | File |
| 1 | Manual > User Manual | Temperature Controllers | SM100 Users manual |
| 2 | Manual > Catalogue | Temperature Controllers | SM100 Catalogue |
| 1 | CAD > 2D | Temperature Controllers | SM100 (2D) |
| 2 | CAD > 3D | Temperature Controllers | SM100 (3D) |
| 1 | Software > Program | ALL | Communication Protocol Examples |
| 2 | Software > Program | ALL | TCS Integrated Communication Program Installation file |
| 3 | Software > Communication data | ALL | TCS Integrated Communication Program Manual(EN) |
| 4 | Software > etc | Temperature Controllers | SM100 EV1.1.0 (ENG) |
| No | Mark | Category | Title | File |
| 1 | Certification > CE | Temperature Controllers | SM100 (EMC) |
| Thermocouple (K), range | -199.9 ℃ ~ 999.9 ℃ |
| RTD (Pt100 Ω), range | -199.9 ℃ ~ 640.0 ℃ |
| (drive voltage | 12 V d.c., load resistance of 600 Ω or more) |