IFM AL4132 is a PerformanceLine Ethernet module designed for EtherCAT communication and 16 digital inputs. It provides decentralized sensor acquisition for high-performance automation systems. The module connects field sensors directly to the EtherCAT network. Integrated high-frequency counters enable local pulse processing. It supports counter functions such as up, down, up/down and direction counting. IP67 protection makes the module suitable for industrial machine environments.
Explore performance details, construction highlights, applications, and technical information in one clear overview.
AL4132 communicates through EtherCAT using 100Base-TX Ethernet technology. EtherCAT provides deterministic communication suitable for high-performance automation. The decentralized field architecture reduces conventional wiring. Sensors can be connected close to their installation points. This improves machine wiring organization and simplifies maintenance. The module is suitable for EtherCAT-enabled PLC and motion-control environments.
The module has 16 digital inputs designed according to IEC 61131-2 Type 2. Eight integrated counters support high-frequency pulse acquisition. Counting frequency can reach 4500 Hz. Main counters provide 32-bit counting capacity while batch counters provide 16-bit capacity. Multiple counter modes provide flexible machine-control functions. IP67 protection supports reliable industrial operation.
16 digital inputs
EtherCAT communication
PerformanceLine construction
Integrated counter function
8 counters
4500 Hz count frequency
32-bit main counter
16-bit batch counter
100Base-TX Ethernet
IP67 protection
M12 industrial connectors
Short-circuit-protected inputs
Robust field housing
Decentralized I/O architecture
Suitable for high-speed automation
EtherCAT automation
Motion-control systems
High-speed machine automation
Production equipment
Conveyor systems
Packaging machinery
Sensor pulse counting
Machine monitoring
Assembly systems
Factory automation
| Specification | Details |
|---|---|
| Product Code | AL4132 |
| Series | PerformanceLine |
| Interface | EtherCAT |
| Digital Inputs | 16 |
| Input Type | IEC 61131-2 Type 2 |
| High Switching Level | 11–30 V |
| Low Switching Level | 0–5 V |
| Input Protection | Short-circuit protected |
| Counter Function | Yes |
| Counter Modes | CTU / CTD / CTUD / CTDIR |
| Number of Counters | 8 |
| Counter Frequency | 4500 Hz |
| Main Counter | 32 bit |
| Batch Counter | 16 bit |
| Ethernet Standard | 100Base-TX |
| Transmission Rate | 100 Mbit/s |
| Communication | EtherCAT |
| Operating Voltage | 20–30 V DC |
| Protection | IP67 |
| Ambient Temperature | -25 to +60 °C |
| Storage Temperature | -25 to +85 °C |
| Humidity | Up to 90% |
| Housing | Polyamide |
| Connector Material | Nickel-plated brass |
| Mounting | Backplane |
| Dimensions | Approx. 208 × 59.3 × 38.4 mm |
| Application | High-speed field automation |