The IFM AL4002 is a field Ethernet I/O module with PROFINET communication and 16 digital inputs. It allows sensors to be connected directly to the fieldbus, helping create a cleaner wiring structure. The module is designed for IP67 field applications. Its robust housing supports use in demanding industrial environments. The integrated high-frequency counter function adds functionality for suitable input signals.
Explore performance details, construction highlights, applications, and technical information in one clear overview.
AL4002 communicates with automation controllers through PROFINET. It supports 100Base-TX Ethernet communication at 100 Mbit/s. PROFINET features include Conformance Class C, S2 redundancy, MRP and supported line/ring topologies. This makes it suitable for modern industrial Ethernet architectures.
The module provides 16 digital inputs for connecting field sensors. The inputs use industrial M12 connections. Digital inputs are designed according to IEC 61131-2 Type 2 requirements. High and low switching levels are defined for reliable sensor signal detection. Short-circuit protection improves input robustness.
AL4002 includes integrated counter functionality. It can be used for applications where pulse signals need to be counted directly at the field module. This can reduce the processing burden on the PLC in suitable applications. Counter functions can support monitoring of rotating or moving equipment. This adds flexibility to decentralized signal acquisition.
The module uses a compact field housing measuring approximately 208 × 59.3 × 38.4 mm. The housing uses polyamide and the sockets use nickel-plated brass. FKM sealing is used for the connector interfaces. The IP67 design supports appropriate field applications.
AL4002 is suitable for machine automation, sensor acquisition and decentralized PROFINET I/O. It can connect multiple digital sensors directly to the network. It is useful in production lines and industrial machines. The high-frequency counter capability can support pulse-counting applications. It provides a practical field I/O solution.
PROFINET interface
16 digital inputs
IP67 protection
M12 field connections
100 Mbit/s Ethernet
PROFINET Conformance Class C
S2 redundancy
MRP support
High-frequency counter function
Short-circuit-protected inputs
PROFINET automation
Digital sensor acquisition
Machine monitoring
Production machinery
Factory automation
Pulse counting
Rotational monitoring
Distributed I/O
Industrial control
| Parameter | Details |
|---|---|
| Product Code | AL4002 |
| Product Type | Ethernet I/O module |
| Interface | PROFINET |
| Digital Inputs | 16 |
| Input Type | Type 2 IEC 61131-2 |
| Operating Voltage | 20...30 V DC |
| Current Consumption | 200...3900 mA |
| Sensor Supply | Up to 3.6 A total |
| Protection Class | III |
| Protection | IP65/IP66/IP67 |
| Ethernet Standard | 100Base-TX |
| Transmission Rate | 100 Mbit/s |
| PROFINET | Supported |
| Conformance | Class C |
| Redundancy | S2 |
| MRP | Supported |
| Counter Function | Yes |
| Counter Functions | CTU/CTD/CTUD/CTDIR |
| Counter Frequency | Up to 4500 Hz |
| Main Counter | 32-bit |
| Batch Counter | 16-bit |
| Dimensions | 208 × 59.3 × 38.4 mm |
| Housing | PA orange |
| Socket | Nickel-plated brass |
| Sealing | FKM |
| Brand | IFM |